A ready to install MPO Female/Male jumper: Customized MPO-24 Jumper, 24-192F, OM4, OM4 50/125μm, Plenum (OFNP)/LSZH. Pre-termination means no polishing, no epoxy and no curing time on site - just route the cable, plug in both ends and bring the link up.
Available lengths are 1m (3ft), 2m (7ft), 3m (10ft), 5m (16ft), 10m (33ft), 15m (49ft), 20m (66ft), 25m (82ft) and 30m (98ft). We can also produce any intermediate or longer length to order, with your choice of labeling and packaging.
| Part Number | XXMPOOM4 |
|---|---|
| Manufacturer | HT |
| Connector A | MPO Female/Male |
| Connector B | MPO Female/Male |
| Polish Type | UPC to UPC |
| Glass Fiber | Bend Insensitive Fiber |
| Fiber Mode | OM4 50/125μm |
| Wavelength | 850/1300nm |
| Trunk Outside Diameter (OD) | 3.0mm-12.0mm |
| Cable Jacket | Plenum (OFNP)/LSZH |
| Connector Durability | 500 times |
| Minimum Bend Radius | 7.5mm |
| Insertion Loss | ≤0.35dB |
| Return Loss | ≥20dB |
| Attenuation at 850nm | ≤2.3dB/km |
| Attenuation at 1300nm | ≤0.6dB/km |
| Operating Temperature | OFNP: -10 to 60°C (14 to 140°F)LSZH: -10 to 70°C (14 to 158°F) |
| Storage Temperature | OFNP: -10 to 70°C (14 to 158°F)LSZH: -20 to 70°C (-4 to 158°F) |
This jumper is intended for high density data center patching. It works equally well in new structured cabling builds and in day-to-day moves, adds and changes where fast, error-free reconnection matters.
Choosing the right polarity is the key to a working MPO link. As a factory we build Type A, Type B and Type C versions of this cable, with male or female connectors on either end. If you are migrating an existing install, send us the current panel layout and we will confirm the correct combination before production.
Please reference XXMPOOM4 in your enquiry. Our sales team can also advise on polarity, gender and jacket choices if your project documentation is not final yet.
We dispatch worldwide by international courier, with air and sea freight options for bulk orders. Goods can be sent collect on your courier account, and documentation for customs clearance is provided with every shipment.
Our test routine covers insertion loss, return loss and ferrule end face inspection on every assembly. Because testing is done in-house, custom variants receive exactly the same verification as standard models.
Each assembly is coiled, capped and sealed in an individual bag, then packed into foam lined export cartons. Test reports can be attached per unit or per batch, and carton marks follow your shipping instructions.